FH085D36E FH110D48E FH110D60EFLF085D36E FLF110D48E FLF110D60EFLR085D36E FLR110D48E FLR110D60EFLR140D60E FC085D36E WARNINGREAD ALL INST
Manual 2100-422Page 8Power Wires: Black (HOT)White (NEUTRAL)Green (GROUND)Control panel(junction boxin FH units)Left sideoil line entranceLef
Manual 2100-422Page 9FIGURE 5TYPICAL FLUE INSTALLATION REQUIREMENTSFRONT FLUE LOWBOY MODEL SHOWN(REPRESENTS ALL MODELS)1/4 inch per 1 foot ri
Manual 2100-422Page 10OIL LINE PIPINGFirst determine whether the pipe system is to be a singleline system or a two line system. All connecti
Manual 2100-422Page 11The following is a detailed explanation of each controlincluded in the Becket AFG Oil Burner, how eachoperates, how to
Manual 2100-422Page 12BECKETT R7184B PRIMARYOPERATIONAL GUIDEPre-Purge Delay – 15 seconds on delayLED Codes – Flashing 1/2 second on / 1/2
Manual 2100-422Page 13FIGURE 7ELECTRONIC BLOWER CONTROLTRANSFORMER 24VSECONDARY CONNECTIONSTHERMOSTATCONNECTIONSOIL PRIMARY T-TCONNECTIONSLIN
Manual 2100-422Page 14BURNER SETUP AND ADJUSTMENTPROCEDURESAll oil burner installations should be performed by aqualified installer in accord
Manual 2100-422Page 15It should be located as close as possible to theoil burner. Care should be taken to prevent airleakage in the oil suct
Manual 2100-422Page 164. FINAL CHECKSM. Measure Stack Temperature Operating theunit at an excessive firing rate will generatemore heat than
Manual 2100-422Page 17FIGURE 8TYPICAL SMOKE – CO2 CHART WITH ADJUSTMENT RANGEToleranceto "knee"Normaladjustmentrange0246881012146&q
CONTENTSGetting Other Information and Publications ... 1Installation and Operating InstructionsEquipment Selection...
Manual 2100-422Page 18FIGURE 9PRESSURE GAUGE CONNECTION TO BLEED PORTMIS-1660Pressure GaugeRemove BleedPort to attachpressure guage.
Manual 2100-422Page 19TABLE 5CORRELATION OF PERCENT OF CO2, O2AND RESERVE AIRnobraCedixoiDnegyxOriAevreseR).xorppA(4.510.515.410.06.02.10.00
Manual 2100-422Page 20SPACING OF ELECTRODESThe electrodes should be spaced 5/32” apart. Theyshould extend 1/16” beyond the end and 5/16” abo
Manual 2100-422Page 21FIGURE 11COMBINATION AIR BOOT ASSEMBLYBURNERASSEMBLYREMOVE PUMP TO ASSEMBLE INNER AIR BOOTUSE THIS KNOCKOUTFOR OIL LINE
Manual 2100-422Page 22APPLIANCES LOCATED IN CONFINEDSPACESIn unconfined spaces in buildings, infiltration may beadequate to provide air for c
Manual 2100-422Page 23ALL VENTILATION AIR FROM OUTDOORSA. The confined space shall be provided with twopermanent openings, one in or near the
Manual 2100-422Page 24FIGURE 14APPLIANCES LOCATED IN CONFINED SPACESALL AIR FROM OUTDOORS THROUGH VENTILATED ATTICMIS-1338NOTE: The inlet an
Manual 2100-422Page 25LOUVERS AND GRILLESIn calculating free area for ventilation and combustionair requirements, consideration shall be give
Manual 2100-422Page 26TABLE 10TEMPERATURE RISE RANGES, LIMIT CONTROL SETTINGS,AND HEATING BLOWER SPEEDSj 70 degree hollow cone spray pattern
Manual 2100-422Page 27AIR FILTERSOnly Lo-Boy models are shipped with air filters. Filterkits are available from your local distributor for U
Manual 2100-422Page 1GETTING OTHER INFORMATION and PUBLICATIONSThese publications can help you install the furnace. Youcan usually find these
Manual 2100-422Page 28LO-BOY MODELS – FILTER LOCATIONSLo-boy models have the filter installed in the return air cabinet section of the furn
Manual 2100-422Page 29MAINTENANCELUBRICATIONNo lubrication is required for either the burner or theblower motor. Both are permanently lubric
Manual 2100-422Page 30COMBINATION COMBUSTIONCHAMBER/BURNER MOUNTINGSYSTEMThe furnace has been designed with a combustionchamber mounting syst
Manual 2100-422Page 31TO REMOVE BURNER ONLYDisconnect fuel line, power cord and wires from T, Ton primary control. Loosen (3) 1/4 inch bolts
Manual 2100-422Page 32PUMP SQUEALS OR CHATTERSThis may be caused by air in pipes. Check all joints inthe oil supply pipe for leaks. Check s
Manual 2100-422Page 33BLOWER SYSTEM RESISTANCE CHARTSCHART 1FH085D36E DATAdeepSrewolBcitatSrewolBwoL01.51.32.03.muideM61.42.43.34.hgiH02.03.
Manual 2100-422Page 34CHART 7FLR140D60E DATAdeepSrewolBcitatSrewolBwoL50.41.71.42.woLmuideM80.71.22.03.hgiHmuideM11.02.72.53.hgiH02.03.04.05
Manual 2100-422Page 35FH SERIESWIRING DIAGRAMWHITEREDORANGEBLUEBLACK12345BLOWER ASSEMBLYGROUNDNEUTRALHOT21123456789BURNER ASS'YTTOIL VAL
Manual 2100-422Page 36FLF/R SERIESWIRING DIAGRAMRETURN AREABLOWER CAPACITORBROWNBROWNBLOWER ASSEMBLY54321BLACKBLUEORANGEREDWHITEBLACKTRANSFOR
Manual 2100-422Page 37FC SERIESWIRING DIAGRAMRETURN AREABLOWER CAPACITOR (5/370)BROWNBROWNBLOWER ASSEMBLY (1/3 HP)54321BLACKBLUEREDWHITE2VALV
Manual 2100-422Page 2INSTALLATION and OPERATING INSTRUCTIONSEQUIPMENT SELECTIONAn accurate heating load calculation must be conductedusing Am
Manual 2100-422Page 3FIGURE 1FLF/R MODELS DIMENSIONSCAHOIL ENTRANCEOPTIONALOIL ENTRANCEOPTIONALLOW VOLTAGEENTRANCEOPTIONALHIGH VOLTAGEENTRAN
Manual 2100-422Page 4FIGURE 2FH MODELS DIMENSIONS 53" (FH085)59" (FH110)23"VESTIBULEDOORFRONT VIEW30 1/2"21 7/8"19
Manual 2100-422Page 5FIGURE 3FC085 MODEL DIMENSIONS54 1/4"23"FLUEKNOCKOUTOPTIONALHIGH VOLTAGEENTRANCEOPTIONALLOW VOLTAGEENTRANCEFR
Manual 2100-422Page 6 IMPORTANTWhen a furnace is installed so that supplyducts carry air circulated by the furnace toareas outside the space
Manual 2100-422Page 7WIRINGFACTORY WIRINGAll units are fully factory wired. Multispeed blowersare factory wired on high speed for cooling/ma